| Model | RC-1202P (Panel-mount) |
|---|---|
| Sensor | CS-12HR (Internal Electrode CA-1202-3RY) CS-12CTPT |
| Flow Cell | CS-1200FC |
| Terminal Box | TR-1200A |
| Measuring Component | Available Chlorine |
| Measuring Range | 100 - 20,000mg/L |
| Repeatability | Within 5% of Full Scale |
| Linearity | Within 5% of Full Scale |
| Analog Output | DC4 - 20mA (Isolated, Max. Load 900ohm) |
| Relay Outputs | Low, High Concentration Alarm Normal Open Error Alarm Normal Close |
| Relay Capacity | AC250V, 1A |
| Dimensions | 199(W)×179(H)×264(D) mm |
| Panel Cutting Size | 192(W)×172(H) mm |
| Weight | 3.5kg |

| Model | RC-1202W (Wall-mount) |
|---|---|
| Sensor | CS-12HR (Internal Electrode CA-1202-3RY) CS-12CTPT |
| Flow Cell | CS-1200FC |
| Terminal Box | TR-1200A |
| Measuring Component | Available Chlorine |
| Measuring Range | 100~20,000mg/L |
| Repeatability | Within 5% of Full Scale |
| Linearity | Within 5% of Full Scale |
| Analog Output | DC4~20mA (Isolated, Max. Load 900ohm) |
| Relay Outputs | Low, High Concentration Alarm Normal Open Error Alarm Normal Close |
| Relay Capacity | AC250V, 1A |
| Dimensions | 265(W)×435(H)×102(D) mm |
| IP Classification Codes | IP 64 |
| Weight | 3.5kg |